How do I meet the new requirement for membrane protection in the 2012 International Residential Code?

2012 International Residential Code (IRC) States:

R501.3 Fire protection of floors. Floor assemblies, not required elsewhere in this code to be fire resistance rated, shall be provided with a ½ inch gypsum wallboard membrane, 5/8 inch wood structural panel membrane, or equivalent on the underside of the floor framing member.

Exceptions:

  1. Floor assemblies located directly over a space protected by an automatic sprinkler system in accordance with Section P2904, NFPA13D, or other approved equivalent sprinkler system. (AWC has developed a guide for partial sprinklering of unfinished basement areas.)
  2. Floor assemblies located directly over a crawl space not intended for storage or fuel-fired appliances.
  3. Portions of floor assemblies can be unprotected when complying with the following:3.1 The aggregate area of the unprotected portions shall not exceed 80 square feet per story.

    3.2 Fire blocking in accordance with Section R302.11.1 shall be installed along the perimeter of the unprotected portion to separate the unprotected portion from the remainder of the floor assembly.

  4. Wood floor assemblies using dimension lumber or structural composite lumber equal to or greater than 2-inch by 10-inch nominal dimension, or other approved floor assemblies demonstrating equivalent fire performance.

The genesis for this requirement was five separate code change proposals introduced in 2009 to revise IRC. The IRC Code Development Committee disapproved all the proposals and requested that the interested parties work together to develop a public comment. In October 2010, the ICC membership approved the above text, jointly developed by the International Association of Fire Fighters, International Association of Fire Chiefs-Life Safety Section, the National Association of Home Builders, and the American Wood Council.

Q: Do I have to specially fire block the perimeter of the opening between the permitted 80 ft² unprotected area and the balance of the protected area?

A: Recent testing with an 80 ft² unprotected area has shown that if a fire occurred under a protected area, fire blocking would provide a minimal level of performance of the membrane system. This affirms the proponents’ intent that the perimeter between the 80 ft² unprotected area and the protected area needs to be fire blocked and no special treatment beyond the specified fire blocking is necessary to achieve the desired performance.

Q: Do I have to treat the joints in the gypsum wallboard with tape and compound?

A: Gypsum wallboard joints are not required to be finished with tape and joint compound. A somewhat analogous requirement in the code is a thermal barrier over foam plastic insulation. Such barriers are also not required to be finished with tape and joint compound. Likewise joints between wood structural panels are not required to be finished with wood filler and sanded.

Q: What was the intent when Clause R501.3, Exception 4 (R302.13 in the 2015 IRC) was developed?

A: As one of the original proponents of this language, AWC has insight into the intent and discussions leading to development of the wording in this exception.

To be considered equivalent to 2×10 sawn lumber or SCL, the framing members should support a load corresponding to 50% of the full bending design of the framing members, while being subjected to an ASTM E 119 time/temperature heating regime. All components utilized in the manufacture of the framing members (fasteners, plates, hardware, etc) should be utilized during testing. The test end criteria should be structural member failure.

AWC believes that the most straightforward and accurate means of determining the required minimum fire resistance time would be to estimate that time using the calculation methodology specified in NDS Chapter 16 for unprotected solid-sawn 2×10 floor joists assuming: a 3-sided exposure, a nominal char rate of 1.5 inches/hr, a bending strength to ASD ratio of 2.85, and supporting a load corresponding to 50% of full bending design.

A white paper entitled “Basis of IRC Membrane Protection Provisions” provides background and commentary on the IRC R501.3 provisions and the method used by the ICC Evaluation Service (ICC-ES) to establish equivalence and compliance with IRC R501.3, Exception 4. 

Q: Do trusses of 2 inch nominal by 10 inch nominal dimension fall within the intent of Exception 4 to Section 501.3 in the 2012 IRC?

A: No. The International Code Council has issued an advisory opinion that Exception 4 does not apply to trusses. Further, the supporting information submitted with the original code change proposal for this section identified where basic membrane protection was to be required and specifically cited unprotected floor/ceiling assemblies using trusses, I-joists, cold formed steel members, and bar joists as structural members needing to meet the membrane requirements. Additionally, the ICC advisory opinion states that assemblies using wood trusses may be approved for exemption if the floor assembly demonstrates equivalent fire performance to floor assemblies using 2×10 lumber. While not noted in the ICC advisory opinion, any other framing system may be approved under Exception 4 by demonstrating equivalent fire performance to floor assemblies using 2×10 lumber.