| 2001 Wood
Frams Construction Manual |
| WS6 1.5 2x6 Wood Stud Wall - Gypsum, Wood Structural Pannel Sheathing, Fiberglass Insulation |
|
|
1. Framing: Nominal 2x6 wood studs, spaced 16 in. o.c., double top plates, single bottom plate
2. Interior Sheathing: 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied vertically. All panel edges backed by framing or blocking.
3. Exterior Sheathing: 3/8 in. wood structural panels (oriented strand board), applied vertically, horizontal joints blocked
4. Gypsum Fasteners: 2-1/4 in. Type S drywall screws, spaced 7 in. o.c.
5. Panel Fasteners: 6d common nails (bright) - 12 in. o.c. in the field, 6 in. o.c. panel edges
6. Insulation: R-19 fiberglass insulation
7. Joints and Fastener Heads: Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound
Test - Tests conducted at the NGC Testing Services, Test No: WP-1408 (Fire Endurance & Hose Stream) on August 13, 2004
Third Party Witness - NGC Testing Services
|
|
|